This checklist is grouped based on the two battery system type:

  • Integrated BESS (Battery Energy Storage System) or
  • Pre-assembled BS (Battery System)

These two systems are the main types of systems classification used in AS/NZ 5139

Expand...
#CER IDQuestionRatingStandards RefY/N?
1BG1Does the battery system appear operational at commencement of audit (for example no warning lights)?Information OnlyN/A
2PV1If a PV array is directly connected to the battery system/inverter, does it appear operational at the commencement of the audit?Information OnlyN/A
3BG3What type of battery system is being audited? - Pre-assembled Integrated BESS (AS/NZS 5139:2019 Section 4) - Pre-assembled BS (AS/NZS 5139:2019 Section 5) - Other (AS/NZS 5139:2019 Section 6) Note: checkInformation OnlyN/A
Expand...

This section applies to installations of lithium-ion pre-assembled integrated Battery Energy Storage System (BESS) as defined in AS/NZS 5139:2019 Clause 4.1.

#CER IDQuestionRatingStandards RefY/N?
1BESS1Where is the lithium-ion pre-assembled integrated BESS installed? What location is it installed in (internal or external)?Information OnlyN/A
2BESS2What is the make of the lithium-ion preassembled integrated BESS?Information OnlyN/A
3BESS3What is the model of the lithium-ion preassembled integrated BESS?Information OnlyN/A
4BESS4What is the serial number of the lithium-ion preassembled integrated BESS?Information OnlyN/A
5BESS5What is the total battery storage capacity in kWh?Information OnlyN/A
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L1Is signage, consisting of circular, green reflector, with the letters “ES”, installed immediately on or adjacent to the meter box and switchboard, and is it readily available to be seen by approaching emergency workers?Medium non-compliance- AS/NZS 5139:2019 Clause 7.3
- Appendix B Clause B2
2SB&L2Is the ES sign at least 100mm in diameter and does it contain the United Nations number for the primary chemistry written below the “ES” lettering – for example, UN3480?Medium non-compliance- AS/NZS 5139:2019 Clause 7.3
- Appendix B Clause B1
3SB&L3If the Battery Energy Storage System is not easily located, is there a plan or drawing showing the location of the Battery Energy Storage System located at the main switchboard which includes the location of shutdown procedures?Medium non-complianceAS/NZS 5139:2019 Clause 7.4
- Appendix B example, Figure B.2
4SB&L4If the Battery Energy Storage System is located adjacent (i.e. next to or adjoining without obstruction and within arm’s reach) to the switchboard and if multiple battery systems or BESS are installed, is there a sign for each that provides an identifiable number together with the total number of systems installed? For example, BESS 1 of 3?Medium non-compliance- AS/NZS5139:2019 Clause 7.6
5SB&L5Is there a Safety Data Sheet (hard copy, not digital) installed within a document holder at the main switchboard or meter box?Medium non-compliance- AS/NZS 5139:2019 Clause 7.3
- Appendix B Clause B1
6SB&L6If battery/inverter system is connected to the main switchboard, has the grid supply main switch been labelled “MAIN SWITCH (GRID)” or similar? Alternatively, if the battery/inverter system has been connected to a distribution board has a sign containing the words “MAIN ISOLATOR (GRID)” or similar been placed adjacent to the isolator for the normal supply to the distribution switchboard?Medium non-compliance- AS/NZS 5139:2019 Clause 7.4
- Appendix B example, Figure B.2
7SB&L8Have supplementary supplies been labelled as “MAIN SWITCH (INVERTER)” at the switchboard to which they are directly connected?Medium non-compliance- AS/NZS 4777.1:2024 Clause 6.3 (a)
8SB&L28Has the main switch for alternative supply from the battery system/inverter been labelled “MAIN SWITCH (ALTERNATIVE)”?Medium non-compliance- AS/NZS 4777.1:2024 Clause 6.3 (d)
9SB&L16Has a warning label been installed at the main switchboard and all intermediate distribution boards to indicate a multimode inverter with alternative supply has been installed and to follow the shutdown procedure for safe isolation, and is the text “Neutral and earth circuits may be live under fault conditions” included on this sign?Rectification required- AS/NZS 4777.1:2024 Clause 6.8
10SB&L17Do switchboards energised by the battery system contain the label “Multiple supplies, isolate all supplies before working on this switchboard”?Medium non-compliance- AS/NZS 4777.1:2024 Clause 6.3 (g)
11SB&L18Where the inverter of the battery system is connected to a distribution board, is the following label present on the main switchboard and all intermediate distribution switchboards: “Warning Multiple Supplies Isolate Inverter Supply at Distribution Switchboard at …”?Rectification required- AS/NZS 4777.1:2024 Clause 6.4
12SB&L19Are circuits that are backed up when the grid is not available appropriately labelled to indicate their function?Medium non-compliance- AS/NZS 3000 Clause 2.10.5.2
- AS/NZS 4777.1:2024 Clause 5.3.6.1
13SB&L25Are all signs and labels:
(a) sufficiently durable and designed to have a lifetime greater than or equal to the service life of the battery system or BESS
(b) constructed of durable materials suitable for the location, and where installed exposed to direct sunlight, shall use UV stabilized materials
(c) fixed in a durable manner
(d) in English
(e) legible and in a letter size appropriate for the location (see guidance in AS/NZS 4777.1 2024 6.1 Note 1)
(f) indelible
(g) visible, as required, at the installed position.
Medium non-compliance- AS/NZS 4777.1:2019 Clause 7.2
- AS/NZS 4777.1:2024 Clause 6.1
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS13Is there a sign adjacent to the lithium-ion preassembled integrated BESS that states:
a) Battery System or Battery Energy Storage System
b) the correct short-circuit current (specifying current in amperes)
c) the correct maximum DC voltage (specifying voltage in volts). For systems over DVC-A, the sign shall also state “Hazardous DC voltage”.
Medium non-compliance- AS/NZS 5139:2019 Clause 7.6
2BESS14Is there a site-specific shutdown procedure that details the sequential steps to safely shutdown the BESS?
The shutdown procedure shall be:
a) installed adjacent to the PCE to which the battery system is connected
b) placed adjacent to and visible from the equipment to be operated in the event of a shutdown.
All labelling of devices shall be consistent with terminology used in the shutdown procedure.
The shutdown procedure shall also state that isolation of the battery system by isolation and shutting down the PCE may not de-energise the battery system and further action may be required
Medium non-compliance- AS/NZS 5139:2019 Clause 7.16
3BESS15If battery chemistry is categorised as a having a risk of battery explosion, has a “Danger, Risk of Battery Explosion” sign been installed in a prominent position approaching the battery system?Medium non-compliance- AS/NZS 5139:2019 Table 3.1
- AS/NZS 5139:2019 Clause 7.8
4BESS16Is the “Danger, toxic fumes” sign installed adjacent to the enclosure or on all doors to the room where the battery system is located detailing the specific fault conditions (for example fire) under which the fumes will be present?
This sign should also include PPE requirements for entering the room/working with the battery system.
Medium non-compliance- AS/NZS 5139:2019 Clause 7.9
5BESS17If the battery chemistry is categorised as having an arc flash hazard above “minor” (see AS/NZS 5139:2019 Clause 6.3.2.2, Table 6.1), is there a sign specifying the dangers of the arc flash? This sign shall be installed either adjacent to the enclosure or on all doors to the room where the battery system is located.Medium non-compliance- AS/NZS 5139:2019 Clause 7.11
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS4Are there any signs of alterations or additions that would result in the lithium-ion preassembled integrated BESS no longer conforming to the Best Practice Guide: Battery Storage Equipment – Electrical Safety Requirements?Rectification required- AS/NZS 5139:2019 Clause 4.4.2.3
2BESS5Are the signs of alterations or additions that make the lithium-ion pre-assembled integrated BESS no longer conforming such that it is unsafe?UnsafeAS/NZS 5139:2019 Clause 4.4.2.3
3BESS11Was the lithium-ion integrated BESS an approved product on the Clean Energy Councils “Approved battery list” at the time of installation?Rectification requiredN/A
4BESS12Has the lithium-ion integrated BESS been recalled by the manufacturer or regulator?Unsafe due to product recallN/A
5BESS18Has the lithium-ion pre-assembled integrated BESS been installed in accordance with manufacturers installation requirements, including reference to the relevant SDS?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.1
6BESS24If installed indoors does the location of the lithium-ion pre-assembled integrated BESS allow access to the connections and any serviceable equipment, doors and panels that are required to be accessed for installation and maintenance?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.2.1 (a)
- AS/NZS 5139:2019 Clause 4.2.5 - 600mm min, 900mm if accessing 230V
7BESS25Does the location of the lithium-ion preassembled integrated BESS conform to the requirements for damp situations defined by AS/NZS 3000:2018 Section 6?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.2.1
- AS/NZS 3000:2018 Section 6
8BESS39If required by the manufacturer of the preassembled integrated BESS, has an earth fault alarm been installed?Rectification required- AS/NZS 5139:2019 Clause 4.3.1.3.2
9BESS43Where the lithium-ion pre-assembled integrated BESS is categorised as having an explosive gas hazard in AS/NZS 5139:2019 Table 3.1, is the installation in accordance with the instructions of the manufacturer including any venting and containment requirements?Rectification required- AS/NZS 5139:2019 Clause 4.3.6
- AS/NZS 5139:2019 Table 3.1
10BESS44Where the lithium-ion pre-assembled integrated BESS is categorised as having a toxic fume hazard in AS/NZS 5139:2019 Table 3.1, is the installation in accordance with the instructions of the manufacturer?Rectification required- AS/NZS 5139:2019 Clause 4.3.7
- AS/NZS 5139:2019 Table 3.1
11BESS45Where the lithium-ion pre-assembled integrated BESS is categorised as having a toxic fume hazard in AS/NZS 5139:2019 Table 3.1, is the installation in accordance with the instructions of the manufacturer?Rectification required- AS/NZS 5139:2019 Clause 4.3.8
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SW&L11Have battery/inverter systems utilising an alternative supply been supplied with an alternative supply main switch in the switchboard they are supplying?Rectification required- AS/NZS 4777.1:2024 Clause 5.3.6.2
2SW&L27Are circuits that are backed up when the grid is not available grouped?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.4.1 & 5.3.4
3SW&L23Are there no more than 2 inverter main switches connected to any 1 switchboard with attached loads?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.5.3.1
4SW&L24Where 2 inverter supplies are connected to a main switchboard or distribution board with other circuits and loads connected, are the inverter main switches grouped together?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.5.3.1
5SW&L33For systems with alternative supply, is anti-islanding maintained, when “MAIN SWITCH(GRID)” is turned off?Unsafe- AS/NZS 4777.1:2024 Clause 8.4.1 (b)
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS19If the battery/inverter is not within 3 meters and line of site of switchboard it is connected to, has an AC isolation device/s, that is able to be secured in the open position, been provided adjacent to the battery/inverter to isolate both supplementary and alternative supplies if applicable?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.3.2 & 5.3.3
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS19If the battery/inverter is not within 3 meters and line of site of switchboard it is connected to, has an AC isolation device/s, that is able to be secured in the open position, been provided adjacent to the battery/inverter to isolate both supplementary and alternative supplies if applicable?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.3.2 & 5.3.3
Overcurrent protection general
#CER IDQuestionRatingStandards RefY/N?
1SB&L10Are all cables related to the battery installation, and not covered by other questions in this checklist, protected against overcurrent?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
2SB&L20Are the inverter/battery supplementary supply cable and associated overcurrent protection device, rated higher than the summation of battery system charging current plus alternative supply overcurrent protection device rating or maximum demand of the alternative supply?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.4.1 & 5.3.4
3SB&L29Are all busbars in the installation rated, or protected against potential overcurrent from summation of grid and supplementary supplies?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
4SB&L30Are all cables in the installation rated, or protected against overcurrent from summation of grid and supplementary supplies?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
5SB&L31Where required, has overcurrent protection been provided for the alternative supply?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
Expand...
#CER IDQuestionRatingStandards RefY/N?

NONE

Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L26Do all AC cables related to the battery installation that pass through penetrations in the switchboard enclosure, pass through a tight fit (less than 5mm diameter) to reduce the spread of fire?Medium non-compliance- AS/NZS 3000:2018 Clause 2.10.7
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS35Is the lithium-ion pre-assembled integrated BESS located on, or placed against the wall, or mounted on the floor within 300mm of the wall or structure separating it from a habitable room, and where the surface of the wall is not made of a suitably non-combustible material, has a suitably non-combustible barrier been placed between the pre-assembled integrated BESS and the surface of the wall or structure to the required dimensions shown in AS/NZS 5139:2019 Figure 4.2?Rectification required- AS/NZS 5139:2019 Clause 4.2.4.2N/A
2BESS36Have all penetrations larger than 5mm through non-combustible material separating the battery system from a habitable room, within dimensions shown in AS/NZS 5139:2019 Figure 5.2, been filled with a fire-retardant material?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.4.2
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS26If installed in a corridor, hallway or lobby does the lithium-ion pre-assembled integrated BESS have at least 1 metre of clearance to allow for safe egress?Rectification required- AS/NZS 5139:2019 Clause 4.2.2.1
2BESS27Is the pre-assembled integrated BESS not installed in any of the below restricted locations?
(a) In restricted locations, as defined for switchboards in AS/NZS 3000.
(b) Within 600 mm of any exit that has an opening 900mm or less.
(c) Within 600 mm of any vertical side of a window or building ventilation that ventilates a habitable room.
(e) Within 900 mm below any of the items included in items (b) and (c).
(f) In ceiling spaces.
(g) In wall cavities.
(h) On roofs, except where specifically deemed suitable.
(i) Under stairways.
(j) Under access walkways.
(k) In an evacuation route or escape route (with less than 1m of safe egress).
Rectification required- AS/NZS 5139:2019 Clause 4.2.2.2
3BESS28Is the lithium-ion pre-assembled integrated BESS installed in a habitable room?Rectification required- AS/NZS 5139:2019 Clause 4.2.2.2
4BESS29Are any fixed appliances not associated with the lithium-ion pre-assembled integrated BESS not installed within the restricted zones shown in AS/NZS 5139:2019 Figure 4.1?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.2.2
5BESS30If the lithium-ion pre-assembled integrated BESS installed does not conform to AS/NZS 60079.14, is the installation not in a location defined to be a hazardous area in AS/NZS 3000:2018 Section 7?Rectification required- AS/NZS 5139:2019 Clause 4.2.2.2
- AS/NZS 60079.14
- AS/NZS 3000:2018 Section 7
6BESS31Is the lithium-ion pre-assembled integrated BESS installed away from hazardous areas for gas cylinders containing heavier-than-air gases and gas relief vent terminals as defined in AS/NZS 3000:2018 Section 4?Rectification required- AS/NZS 5139:2019 Clause 4.2.2.2
- AS/NZS 3000:2018 Section 4
7BESS32Is the lithium-ion pre-assembled integrated BESS installed in a location that will not expose it to temperatures lower than the minimum or greater than the maximum temperatures as specified by the manufacturer?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.3
- AS/NZS 5139:2019 Clause 4.2.3.2
8BESS33Is the lithium-ion pre-assembled integrated BESS installed in a location where it can be protected against damage that might reasonably be expected from the presence of water, high humidity, dust, vermin or direct sunlight?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.3
- AS/NZS 5139:2019 Clause 4.2.3.2
9BESS34Is the lithium-ion pre-assembled integrated BESS installed in a location that will not expose it to localised or general heat sources? This may include direct sunlight, generators, stream pipes, hot water systems, air conditioners or space heaters. There should also be no direct airflow from any appliance directed at it.Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.3
- AS/NZS 5139:2019 Clause 4.2.3.2
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L7What is the size of circuit breaker controlling “MAIN SWITCH (GRID)?”Information OnlyN/A
1SB&L9What is the size of circuit breaker controlling “Main Switch Inverter” and/or “Main Switch Alternative”?Information OnlyN/A
1SB&L12Is there an alternative supply from the BESS/inverter?Information OnlyN/A
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L13Do the alternative supply circuits have appropriate RCD protection?Rectification required- AS/NZS 4777.1:2024 Clause 5.3.6.4
- AS/NZS 3000:2018 amendment 2 Clause 2.6.3.2.5 (a)
2SB&L14Are there any parallel earth-neutral (secondary MEN) connections present in the battery system/inverter or associated wiring?Rectification required- AS/NZS 4777.1:2024 Clause 8.3.3.2.2 & 8.3.3.3.2.
- AS/NZS 3000:2018 Clause 8.3.7.2 (f)
3SB&L15Is neutral continuity maintained for all circuits provided and operating on an alternative supply?UnsafeAS/NZS 4777.1:2024 Clause 5.3.2.2 & 8.3.4.4.2
4SB&L21After turning on the “MAIN SWITCH (INVERTER)” does it take greater than 60 seconds for current to be shown on the supplementary supply active conductor?Medium non-compliance- AS/NZS 4777.1:2024 Clause 8.4.1 (a)
5SB&L22After turning off the “MAIN SWITCH (INVERTER)” does it take less than 2 seconds for current to dissipate from the supplementary supply active conductor?Rectification required- AS/NZS 4777.1:2024 Clause 8.4.1 (b)
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BESS20Is the AC interconnection of the lithium-ion pre-assembled integrated BESS to the switchboard or distribution board in accordance with AS/NZS 3000? If not, does the defect pose a potential safety risk at some stage in the life time of the system?Rectification required- AS/NZS 5139:2019 Clause 4.2.1
- AS/NZS 5139:2019 Clause 4.3.1.1
2BESS21Is the AC interconnection of the lithium-ion pre-assembled integrated BESS to the switchboard or distribution board in accordance with AS/NZS 3000? If not, is the defect not likely to cause a potential safety risk at some stage in the life of the system?Medium non-compliance- AS/NZS 5139:2019 Clause 4.2.1
- AS/NZS 5139:2019 Clause 4.3.1.1
3BESS22If the AC interconnection of the lithium-ion pre-assembled integrated BESS to the switchboard or distribution board is not in accordance with AS/NZS 3000, is it such that it constitutes a safety hazard which poses an imminent risk?Unsafe- AS/NZS 5139:2019 Clause 4.2.1
- AS/NZS 5139:2019 Clause 4.3.1.1
4BESS37Do all grid connections of the pre-assembled BESS meet the requirements of AS/NZS 4777.1?Medium non-compliance- AS/NZS 5139:2019 Clause 4.3.1.2
- AS/NZS 4777.1:2024
5BESS38Has the earthing of the lithium-ion pre-assembled integrated BESS been installed to manufacturers requirements and meet the earthing requirements in AS/NZS 3000?Rectification required- AS/NZS 5139:2019 Clause 4.3.1.3.1
- AS/NZS 3000
6BESS46Are there any accessible live parts? Are any live parts in direct contact with any equipment, component, terminals or connection, that are tested to be LIVE and accessible by one action to be touched?Unsafe- AS/NZS 3000
7BESS47Are there connectors, couplings, covers or components able to be removed without the use of a tool which provide access to live parts?Rectification required- AS/NZS 3000
8BESS48Has all electrical work associated with the installation of the lithium-ion pre-assembled integrated BESS been installed in line with Australian standards? If not, is the defect likely to pose a potential safety risk at some stage in the lifetime of the system?Rectification required- AS/NZS 3000:2018
- AS/NZS 5139:2019
- AS/NZS 5033:2021
- AS/NZS 4777.1:2024
9BESS49Has any electrical work associated with the installation of the lithium-ion pre-assembled integrated BESS not been installed in line with Australian standards such that it is not likely to cause a potential safety hazard now or for the expected lifetime of the system?Medium non-compliance- AS/NZS 3000:2018
- AS/NZS 5139:2019
- AS/NZS 5033:2021
- AS/NZS 4777.1:2024
10BESS50Has any electrical work associated with the installation of the lithium-ion pre-assembled integrated BESS not been installed in line with Australian standards such that it constitutes a safety hazard which poses an imminent risk?Unsafe- AS/NZS 3000
11BESS51Are there any loose connections in the pre-assembled integrated BESS and associated wiring with no signs of heat?Rectification required- AS/NZS 3000
12BESS52Are there any loose connections in the pre-assembled integrated BESS and associated wiring with signs of heat?Unsafe- AS/NZS 3000
Expand...
#CER IDQuestionRatingStandards RefY/N?
1DOC1Has a full system manual incorporating all components of AS/NZS 5139:2019 Clause 6.4.1.2 been provided to the home owner?Medium non-complianceAS/NZS 5139:2019 Clause 6.4.1.2
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BG1Does the battery system appear operational at commencement of audit (for example no warning lights)?Information OnlyN/A
2PV1If a PV array is directly connected to the battery system/inverter, does it appear operational at the commencement of the audit?Information OnlyN/A
3BG3What type of battery system is being audited? - Pre-assembled Integrated BESS (AS/NZS 5139:2019 Section 4) - Pre-assembled BS (AS/NZS 5139:2019 Section 5) - Other (AS/NZS 5139:2019 Section 6) Note: checkInformation OnlyN/A
Expand...

This section applies to installations of a lithium-ion pre-assembled Battery System (BS) as defined in AS/NZS 5139:2019 Clause 5.1.

#CER IDQuestionRatingStandards RefY/N?
1BS6Where is the lithium-ion pre-assembled BS installed?Information OnlyN/A
2BS7What is the make of the lithium-ion preassembled BS?Information OnlyN/A
3BS8What is the model of the lithium-ion preassembled BS?Information OnlyN/A
4BS9What is the serial number of the inverter that the battery system is connected to?Information OnlyN/A
5BS10What is the serial number of the lithium-ion preassembled BS?Information OnlyN/A
6BS11What is the total battery storage capacity in kWh?Information OnlyN/A
7BS14What is the Decisive Voltage Classification (DVC) of the lithium-ion pre-assembled BS?
- DVC-A <60 Volts DC
- DVC-B <120 Volts DC
- DVC-C >120 Volts DC
Information OnlyN/A
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L1Is signage, consisting of circular, green reflector, with the letters “ES”, installed immediately on or adjacent to the meter box and switchboard, and is it readily available to be seen by approaching emergency workers?Medium non-compliance- AS/NZS 5139:2019 Clause 7.3
- Appendix B Clause B2
2SB&L2Is the ES sign at least 100mm in diameter and does it contain the United Nations number for the primary chemistry written below the “ES” lettering – for example, UN3480?Medium non-compliance- AS/NZS 5139:2019 Clause 7.3
- Appendix B Clause B1
3SB&L3If the Battery Energy Storage System is not easily located, is there a plan or drawing showing the location of the Battery Energy Storage System located at the main switchboard which includes the location of shutdown procedures?Medium non-complianceAS/NZS 5139:2019 Clause 7.4
- Appendix B example, Figure B.2
4SB&L4If the Battery Energy Storage System is located adjacent (i.e. next to or adjoining without obstruction and within arm’s reach) to the switchboard and if multiple battery systems or BESS are installed, is there a sign for each that provides an identifiable number together with the total number of systems installed? For example, BESS 1 of 3?Medium non-compliance- AS/NZS5139:2019 Clause 7.6
5SB&L5Is there a Safety Data Sheet (hard copy, not digital) installed within a document holder at the main switchboard or meter box?Medium non-compliance- AS/NZS 5139:2019 Clause 7.3
- Appendix B Clause B1
6SB&L6If battery/inverter system is connected to the main switchboard, has the grid supply main switch been labelled “MAIN SWITCH (GRID)” or similar? Alternatively, if the battery/inverter system has been connected to a distribution board has a sign containing the words “MAIN ISOLATOR (GRID)” or similar been placed adjacent to the isolator for the normal supply to the distribution switchboard?Medium non-compliance- AS/NZS 5139:2019 Clause 7.4
- Appendix B example, Figure B.2
7SB&L8Have supplementary supplies been labelled as “MAIN SWITCH (INVERTER)” at the switchboard to which they are directly connected?Medium non-compliance- AS/NZS 4777.1:2024 Clause 6.3 (a)
8SB&L28Has the main switch for alternative supply from the battery system/inverter been labelled “MAIN SWITCH (ALTERNATIVE)”?Medium non-compliance- AS/NZS 4777.1:2024 Clause 6.3 (d)
9SB&L16Has a warning label been installed at the main switchboard and all intermediate distribution boards to indicate a multimode inverter with alternative supply has been installed and to follow the shutdown procedure for safe isolation, and is the text “Neutral and earth circuits may be live under fault conditions” included on this sign?Rectification required- AS/NZS 4777.1:2024 Clause 6.8
10SB&L17Do switchboards energised by the battery system contain the label “Multiple supplies, isolate all supplies before working on this switchboard”?Medium non-compliance- AS/NZS 4777.1:2024 Clause 6.3 (g)
11SB&L18Where the inverter of the battery system is connected to a distribution board, is the following label present on the main switchboard and all intermediate distribution switchboards: “Warning Multiple Supplies Isolate Inverter Supply at Distribution Switchboard at …”?Rectification required- AS/NZS 4777.1:2024 Clause 6.4
12SB&L19Are circuits that are backed up when the grid is not available appropriately labelled to indicate their function?Medium non-compliance- AS/NZS 3000 Clause 2.10.5.2
- AS/NZS 4777.1:2024 Clause 5.3.6.1
13SB&L25Are all signs and labels:
(a) sufficiently durable and designed to have a lifetime greater than or equal to the service life of the battery system or BESS
(b) constructed of durable materials suitable for the location, and where installed exposed to direct sunlight, shall use UV stabilized materials
(c) fixed in a durable manner
(d) in English
(e) legible and in a letter size appropriate for the location (see guidance in AS/NZS 4777.1 2024 6.1 Note 1)
(f) indelible
(g) visible, as required, at the installed position.
Medium non-compliance- AS/NZS 4777.1:2019 Clause 7.2
- AS/NZS 4777.1:2024 Clause 6.1
Labelling specifics
#CER IDQuestionRatingStandards RefY/N?
1BS15Is there a sign adjacent to the lithium-ion preassembled BS that states:
a) Battery System or Battery Energy Storage System
b) the correct short-circuit current (specifying current in amperes)
c) the correct maximum DC voltage (specifying voltage in volts).

For systems over DVC-A, the sign shall also state “Hazardous DC voltage”.
Medium non-compliance- AS/NZS 5139:2019 Clause 7.6
2BS16Is there a site-specific shutdown procedure that details the sequential steps to safely shutdown the BS? The shutdown procedure shall be:
a) installed adjacent to the PCE to which the battery system is connected
b) placed adjacent to and visible from the equipment to be operated in the event of a shutdown. All labelling of devices shall be consistent withterminology used in the shutdown procedure.

The shutdown procedure shall also state that isolation of the battery system by isolation and shutting down the PCE may not de-energise the battery system and further action may be required.
Medium non-compliance- AS/NZS 5139:2019 Clause 7.16
3BS18Where multiple energy sources (for example solar and battery) are connected to the one inverter, has a warning sign been installed to indicate all energy sources be turned off to achieve complete isolation?Medium non-compliance- AZ/NZS 4777.1:2024 Clause 6.11.1
4BS19If battery chemistry is categorised as a having a risk of battery explosion, has a “Danger, Risk of Battery Explosion” sign been installed in a prominent position approaching the battery system?Medium non-compliance- AS/NZS 5139:2019 Table 3.1
- AS/NZS 5139:2019 Clause 7.8
5BS20Is the “Danger, toxic fumes” sign installed adjacent to the enclosure or on all doors to the room where the battery system is located and does it detail the specific fault conditions (for example fire) under which the fumes will be present?

This sign should also include PPE requirements for entering the room/working with the battery system.
Medium non-compliance- AS/NZS 5139:2019 Clause 7.9
6BS21If the battery chemistry is categorised as having an arc flash hazard above “minor” (see AS/NZS 5139 6.3.2.2 Table 6.1), is there a sign specifying the dangers of the arc flash? This sign shall be installed either adjacent to the enclosure or on all doors to the room where the battery system is located.Medium non-compliance- AS/NZS 5139:2019 Clause 7.11
7BS98Has DC battery system cabling or enclosures containing battery system cabling between the battery system and inverter been labelled with the word “BATTERY” at intervals not exceeding 2m?Medium non-compliance- AS/NZS 5139:2019 Clause 7.14
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BS4Are there any signs of alterations or additions that would result in the lithium-ion preassembled BS no longer conforming to the Best Practice Guide: Battery Storage Equipment - Electrical Safety Requirements? https://cleanenergycouncil.org.au/industryprograms/products-program/batteriesRectification required- AS/NZS 5139:2019 Clause 5.4.2.3
2BS5Are the signs of alterations or additions that make the lithium-ion pre-assembled BS no longer conforming such that it is unsafe?Unsafe- AS/NZS 5139:2019 Clause 5.4.2.3
3BS12Was the lithium-ion pre-assembled BS an approved product on the Clean Energy Council’s “Approved battery list” at the time of installation?
https://cer.gov.au/document_page/cecapproved-solar-batteries
https://cleanenergycouncil.org.au/industryprograms/products-program/batteries
Rectification requiredN/A
4BS13Has the lithium-ion integrated BESS been recalled by the manufacturer or regulator?Unsafe due to product recall- AS/NZS 5139:2019 Clause 5.4
5BS22Has the lithium-ion pre-assembled BS been installed in accordance with manufacturers installation requirements, including reference to the relevant SDS?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.1
6BS24If installed indoors does the location of the lithium-ion pre-assembled integrated BESS allow access to the connections and any serviceable equipment, doors and panels that are required to be accessed for installation and maintenance?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.2.1 (a)
- AS/NZS 5139:2019 Clause 5.2.5 See line 49
7BS25Does the location of the lithium-ion preassembled BS conform to the requirements for damp situations defined by AS/NZS 3000:2018 Section 6?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.2.1
- AS/NZS 3000:2018 Section 6
8BS38If the lithium-ion pre-assembled BS is located in a room, is the room clean, dry and ventilated?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.5
9BS39If the lithium-ion pre-assembled BS is located in a room, does the room provide and maintain protection against detrimental environmental conditions and other external factors?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.5
10BS40If the lithium-ion pre-assembled BS is located in a room, is the room suitable to minimise the likelihood of a build-up insect or vermin infestation or other materials on or around the lithium-ion pre-assembled BS?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.5
11BS41If the lithium-ion pre-assembled BS is located in a room, does the size of the room allow for sufficient clearance around the lithium-ion preassembled BS to provide safe handling and access for installation, removal and maintenance? The minimum unimpeded access shall be:
a) 900 mm with the doors open
b) 600 mm with the doors open for battery
Systems that have:
i) voltage no greater than DVC-A; and
ii) a calculated arc flash energy at the output terminals of the battery system not greater than 4.0 cal/cm², or
iii) the clearance specified by the manual.
Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.5
12BS84Does the lithium-ion pre-assembled BS separated from earth have an alarm system provided that will cause an action to be initiated to correct the fault? This could be audible, visual or via an electronic communicationMedium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.8
13BS85Has the lithium-ion pre-assembled BS been installed in accordance with manufacturer’s instructions to limit the exposure to an arc flash hazard during installation and for maintenance?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.2
14BS88Where the lithium-ion pre-assembled BS is categorised as having an explosive gas hazard in AS/NZS 5139:2019 Table 3.1, is the installation in accordance with the instructions of the manufacturer including any venting and containment requirements?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.6
- AS/NZS 5139:2019 Table 3.1
15BS89Where the lithium-ion pre-assembled BS is categorised as having a toxic fume hazard in AS/NZS 5139:2019 Table 3.1, is the installation in accordance with the instructions of the manufacturer?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.7
- AS/NZS 5139:2019 Table 3.2
16BS90Does the lithium-ion pre-assembled BS have an alarm system provided that will cause an action to be initiated to correct the fault? This could be audible, visual or via an electronic communication.Rectification required- AS/NZS 5139:2019 Clause 5.3.8
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SW&L11Have battery/inverter systems utilising an alternative supply been supplied with an alternative supply main switch in the switchboard they are supplying?Rectification required- AS/NZS 4777.1:2024 Clause 5.3.6.2
2SW&L27Are circuits that are backed up when the grid is not available grouped?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.4.1 & 5.3.4
3SW&L23Are there no more than 2 inverter main switches connected to any 1 switchboard with attached loads?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.5.3.1
4SW&L24Where 2 inverter supplies are connected to a main switchboard or distribution board with other circuits and loads connected, are the inverter main switches grouped together?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.5.3.1
5SW&L33For systems with alternative supply, is anti-islanding maintained, when “MAIN SWITCH(GRID)” is turned off?Unsafe- AS/NZS 4777.1:2024 Clause 8.4.1 (b)
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BS17If the battery/inverter is not within 3 meters and line of site to the switchboard it is connected, has an AC isolation device/s, that is able to be secured in the open position, been provided adjacent to the battery/inverter to isolate both supplementary and alternative supplies if applicable?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.3.2 & 5.3.3
2BS50Has a means of disconnection been installed to isolate the pre-assembled BS from the PCE and vice versa, to allow for maintenance, repair, fault finding and inspection tasks to be carried out safely?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.1
3BS51Is it possible to isolate the PCE from all poles of the pre-assembled BS using one of the following load breaking disconnection methods installed?
a) An adjacent and physically separate disconnection device.
b) A disconnection device integrated into the PCE.
c) A disconnection device integrated into the pre-assembled BS.
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.2
4BS52If a switch-disconnector has been used as the load breaking disconnection device, does it meet the following requirements:
a) conform to AS 60947.3
b) be of the non-polarised type
c) be DC rated
d) have a voltage rating than the battery system’s maximum voltage under all operating conditions
e) be rated to withstand the maximum short-circuit current
f) have a current rating greater than the maximum DC current for the BESS
g) be rated to interrupt for full load
h) meet the requirements of AS/NZS 3000:2018 Section 2 for isolating device selection
i) be rated for independent manual operation
j) have a minimum pollution degree 3 classification
k) be able to be secured in the open position and only secured when the main contacts are in the open position
l) conform to requirements for isolation including marking requirements for an isolation device
m) have a utilization category of at least DC21B.
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.3
5BS53If an adjacent or physically separated disconnection device is installed indoors, is the disconnection device mounted in an enclosure that has a minimum IP 23 rating?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.4
6BS54If an adjacent or physically separated disconnection device is installed outdoors, is the disconnection device mounted in an enclosure that has a minimum IP 56NW when tested under the conditions of AS 60947.3:2018 Clause D.8.3.13.4, D.8.13.3.5, D.8.3.13.6, D.8.3.13.7 and D.8.3.13.8 (in Australian variations Appendix ZZ)?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.4
7BS55Are the switch-disconnectors for outdoor use suitably rated for an ambient temperature of 40 degrees Celsius?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.4
8BS56If the disconnection device is integrated in the PCE does it meet one of the following additional requirements:
a) an isolation device that is mechanically interlocked with a replaceable module of the PCE, and allows the module to be removed from the section containing the isolation device without risk of electric hazards
b) an isolation device is located in the same enclosure as the other components of the PCE. With the isolation device in the off position there shall be no risk of electric hazard when any PCE external enclosure cover is removed for repair or replacement of other components of the PCE.
Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.5
9BS57If the pre-assembled BS includes an internal isolation device operation in all live conductors, is it readily accessible and does it provide the same functions as for an adjacent external isolation device? No additional adjacent external isolation device is required.Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.6
10BS58Is the isolation device readily accessible?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.7
11BS59Where the cables connecting the pre-assembled BS and PCEs are less than 2m in length, is the isolation device(s) installed adjacent to either the pre-assembled battery system or the PCE?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.7
12BS60Where the cables connecting the pre-assembled BS and PCE are greater than 2m in length, is the isolation device installed at both the pre-assembled battery system and PCE?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.7
13BS61If there are multiple PCEs (for example a solar charge controller and an inverter; or multiple inverters), have separate isolation devices been installed?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.8
14BS62If there are two or more lithium-ion pre-assembled battery systems connected in parallel, does each one have a separate isolation device?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.8
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BS17If the battery/inverter is not within 3 meters and line of site to the switchboard it is connected, has an AC isolation device/s, that is able to be secured in the open position, been provided adjacent to the battery/inverter to isolate both supplementary and alternative supplies if applicable?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.3.2 & 5.3.3
2BS50Has a means of disconnection been installed to isolate the pre-assembled BS from the PCE and vice versa, to allow for maintenance, repair, fault finding and inspection tasks to be carried out safely?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.1
3BS51Is it possible to isolate the PCE from all poles of the pre-assembled BS using one of the following load breaking disconnection methods installed?
a) An adjacent and physically separate disconnection device.
b) A disconnection device integrated into the PCE.
c) A disconnection device integrated into the pre-assembled BS.
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.2
4BS52If a switch-disconnector has been used as the load breaking disconnection device, does it meet the following requirements:
a) conform to AS 60947.3
b) be of the non-polarised type
c) be DC rated
d) have a voltage rating than the battery system’s maximum voltage under all operating conditions
e) be rated to withstand the maximum short-circuit current
f) have a current rating greater than the maximum DC current for the BESS
g) be rated to interrupt for full load
h) meet the requirements of AS/NZS 3000:2018 Section 2 for isolating device selection
i) be rated for independent manual operation
j) have a minimum pollution degree 3 classification
k) be able to be secured in the open position and only secured when the main contacts are in the open position
l) conform to requirements for isolation including marking requirements for an isolation device
m) have a utilization category of at least DC21B.
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.3
5BS53If an adjacent or physically separated disconnection device is installed indoors, is the disconnection device mounted in an enclosure that has a minimum IP 23 rating?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.4
6BS54If an adjacent or physically separated disconnection device is installed outdoors, is the disconnection device mounted in an enclosure that has a minimum IP 56NW when tested under the conditions of AS 60947.3:2018 Clause D.8.3.13.4, D.8.13.3.5, D.8.3.13.6, D.8.3.13.7 and D.8.3.13.8 (in Australian variations Appendix ZZ)?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.4
7BS55Are the switch-disconnectors for outdoor use suitably rated for an ambient temperature of 40 degrees Celsius?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.4
8BS56If the disconnection device is integrated in the PCE does it meet one of the following additional requirements:
a) an isolation device that is mechanically interlocked with a replaceable module of the PCE, and allows the module to be removed from the section containing the isolation device without risk of electric hazards
b) an isolation device is located in the same enclosure as the other components of the PCE. With the isolation device in the off position there shall be no risk of electric hazard when any PCE external enclosure cover is removed for repair or replacement of other components of the PCE.
Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.5
9BS57If the pre-assembled BS includes an internal isolation device operation in all live conductors, is it readily accessible and does it provide the same functions as for an adjacent external isolation device? No additional adjacent external isolation device is required.Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.6
10BS58Is the isolation device readily accessible?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.3.7
11BS59Where the cables connecting the pre-assembled BS and PCEs are less than 2m in length, is the isolation device(s) installed adjacent to either the pre-assembled battery system or the PCE?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.7
12BS60Where the cables connecting the pre-assembled BS and PCE are greater than 2m in length, is the isolation device installed at both the pre-assembled battery system and PCE?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.7
13BS61If there are multiple PCEs (for example a solar charge controller and an inverter; or multiple inverters), have separate isolation devices been installed?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.8
14BS62If there are two or more lithium-ion pre-assembled battery systems connected in parallel, does each one have a separate isolation device?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.3.8
Overcurrent protection general
#CER IDQuestionRatingStandards RefY/N?
1SB&L10Are all cables related to the battery installation, and not covered by other questions in this checklist, protected against overcurrent?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
2SB&L20Are the inverter/battery supplementary supply cable and associated overcurrent protection device, rated higher than the summation of battery system charging current plus alternative supply overcurrent protection device rating or maximum demand of the alternative supply?Medium non-compliance- AS/NZS 4777.1:2024 Clause 3.4.1 & 5.3.4
3SB&L29Are all busbars in the installation rated, or protected against potential overcurrent from summation of grid and supplementary supplies?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
4SB&L30Are all cables in the installation rated, or protected against overcurrent from summation of grid and supplementary supplies?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
5SB&L31Where required, has overcurrent protection been provided for the alternative supply?Rectification required- AS/NZS 4777.1:2024 Clause 3.4.2
- AS/NZS 3000:2018 Clause 2.5.3.1
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BS43Is overcurrent protection installed in all live conductors, excluding control and monitoring circuits?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.2.1
2BS44If installed, is the DC overcurrent protection device installed adjacent to the battery system and:
a) is it of a non-polarised type
b) is it DC rated
c) does it have a voltage rating greater than the battery system’s maximum voltage under all normal and abnormal conditions
d) does it meet the requirements of AS/NZS 3000:2018 Section 2
e) does it have a current rating to protect the cabling from the pre-assembled battery system?
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.2.1
3BS45Where a DC overcurrent protective device is not integrated into the lithium-ion pre-assembled BS, has either a HRC fuse or miniature circuit breaker that meets the requirements of AS/NZS 5139:2019 Clause 5.3.1.2.1 been installed?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.2.1
4BS46If the DC overcurrent protection device is a circuit breaker, does it meet the requirements of AS/NZS 5139:2019 Clause 5.3.1.2.2?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.2.1
- AS/NZS 5139:2019 Clause 5.3.1.2.2
5BS47If the DC overcurrent protection device is a HRC fuse, does it meet the requirements of AS/NZS 5139:2019 Clause 5.3.1.2.3?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.2.1
- AS/NZS 5139:2019 Clause 5.3.1.2.3
6BS48Where the DC overcurrent protective device is integrated into the lithium-ion pre-assembled BS and is being used to protect the DC cables between the battery system inverter, does it meet all of the following requirements:
- Readily available circuit breaker or HRC fuse.
- Operates on both the positive and negative conductors.
- Rated lower than the current carrying capacity of the DC cables between the battery system and the inverter.
- Permitted by the battery manufacturer to protect the outgoing cables between the battery system and inverter.
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.2.1
- AS/NZS 5139:2019 Clause 5.3.1.2.4
7BS49If the DC overcurrent protection device is external, is it installed as close as practical to the output terminals of the battery system and no greater than 2m away?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.2.5
8BS73Is the current-carrying capacity of the pre-assembled BS cables to the PCE greater than the rating of the overcurrent protection device installed?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.5
9BS75Has overcurrent protection been installed on the pre-assembled BS’s DC port of the PCE if:
a) the PCE charging current or load current under fault conditions is greater than the current-carrying capacity of the conductor between the PCE and the pre-assembled BS
- b) the length of the cable between the PCE and the pre-assembled BS overcurrent device is greater than 3m?
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.7
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L26Do all AC cables related to the battery installation that pass through penetrations in the switchboard enclosure, pass through a tight fit (less than 5mm diameter) to reduce the spread of fire?Medium non-compliance- AS/NZS 3000:2018 Clause 2.10.7
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BS35If the lithium-ion pre-assembled BS is located on, or placed against the wall, or mounted on the floor within 300mm of the wall or structure separating it from a habitable room, and the surface of the wall is not made of a suitably non-combustible material, has a suitable non-combustible barrier has been placed between the pre-assemble integrated BESS and the surface of the wall or structure to the required dimensions shown in AS/NZS 5139:2019 Figure 4.2?Rectification required- AS/NZS 5139:2019 Clause 5.2.4.2
- AS/NZS 5139:2019 Figure 5.2
2BS36Have all penetrations larger than 5mm through non-combustible material separating the battery system from a habitable room, within dimensions shown in AS/NZS 5139:2019 Figure 5.2, been filled with a fire-retardant material?Medium non-compliance- AS/NZS 5139:2019 Clause 5.2.4.2
- AS/NZS 5139:2019 Figure 5.2
Expand...
#CER IDQuestionRatingStandards RefY/N?
1BS26If installed in a corridor, hallway or lobby does the lithium-ion pre-assembled BS have at least one metre of clearance to allow for safe egress?Rectification required- AS/NZS 5139:2019 Clause 5.2.2.1
2BS27Is the pre-assembled integrated BS not installed in any of the below restricted locations?
(a) In restricted locations, as defined for switchboards in AS/NZS 3000.
(b) Within 600 mm of any exit that has an opening 900mm or less.
(c) Within 600 mm of any vertical side of a window or building ventilation that ventilates a habitable room.
(e) Within 900 mm below any of the items included in items (b) and (c).
(f) In ceiling spaces.
(g) In wall cavities.
(h) On roofs, except where specifically deemed suitable.
(i) Under stairways.
(j) Under access walkways.
(k) In an evacuation route or escape route (with less than 1m of safe egress).
Rectification required- AS/NZS 5139:2019 Clause 5.2.2.2
3BS28Is the lithium-ion pre-assembled BS installed in a habitable room?Rectification requiredAS/NZS 5139:2019 Clause 5.2.2.2
4BS29Are any fixed appliances not associated with the lithium-ion pre-assembled BS not installed within the restricted zones shown in AS/NZS 5139:2019 Figure 5.1?Medium non-compliant- AS/NZS 5139:2019 Clause 5.2.2.2
- AS/NZS 5139:2019 Figure 5.1
5BS30If the lithium-ion pre-assembled BS installed does not conform to AS/NZS 60079.14, is the installation away from a location defined to be a hazardous area in AS/NZS 3000:2018 Section 7?Rectification required- AS/NZS 5139:2019 Clause 5.2.2.2
- AS/NZS 60079.14
- AS/NZS 3000:2018 Section 7
6BS31Is the lithium-ion pre-assembled BS installed away from hazardous areas for gas cylinders containing heavier-than-air gases and gas relief vent terminals as defined in AS/NZS 3000:2018 Section 4?Rectification required- AS/NZS 5139:2019 Clause 5.2.2.2
- AS/NZS 3000:2018 Section 4
7BS32Is the lithium-ion pre-assembled BS installed in a location that will not expose it to temperatures lower than the minimum or greater than the maximum temperatures as specified by the manufacturer?Medium non-compliant- AS/NZS 5139:2019 Clause 5.2.3
- AS/NZS 5139:2019 Clause 5.2.3.2
8BS33Is the lithium-ion pre-assembled BS installed in a location where it can be protected against damage that might reasonably be expected from the presence of water, high humidity, dust, vermin or direct sunlight?Medium non-compliant- AS/NZS 5139:2019 Clause 5.2.3
- AS/NZS 5139:2019 Clause 5.2.3.2
9BS34Is the lithium-ion pre-assembled BS installed in a location that will not expose it to localised or general heat sources? This may include direct sunlight, generators, stream pipes, hot water systems, air conditioners or space heaters. There should also be no direct airflow from any appliance directed at it.Medium non-compliant- AS/NZS 5139:2019 Clause 5.2.3
- AS/NZS 5139:2019 Clause 5.2.3.2
10BS37If the lithium-ion pre-assembled BS is located in a room, is it located so that access to the battery system is not obstructed by the structure of the building, fixtures and fittings within the room?Medium non-compliant- AS/NZS 5139:2019 Clause 5.2.5
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L7What is the size of circuit breaker controlling “MAIN SWITCH (GRID)?”Information OnlyN/A
1SB&L9What is the size of circuit breaker controlling “Main Switch Inverter” and/or “Main Switch Alternative”?Information OnlyN/A
1SB&L12Is there an alternative supply from the BESS/inverter?Information OnlyN/A
Expand...
#CER IDQuestionRatingStandards RefY/N?
1SB&L13Do the alternative supply circuits have appropriate RCD protection?Rectification required- AS/NZS 4777.1:2024 Clause 5.3.6.4
- AS/NZS 3000:2018 amendment 2 Clause 2.6.3.2.5 (a)
2SB&L14Are there any parallel earth-neutral (secondary MEN) connections present in the battery system/inverter or associated wiring?Rectification required- AS/NZS 4777.1:2024 Clause 8.3.3.2.2 & 8.3.3.3.2.
- AS/NZS 3000:2018 Clause 8.3.7.2 (f)
3SB&L15Is neutral continuity maintained for all circuits provided and operating on an alternative supply?UnsafeAS/NZS 4777.1:2024 Clause 5.3.2.2 & 8.3.4.4.2
4SB&L21After turning on the “MAIN SWITCH (INVERTER)” does it take greater than 60 seconds for current to be shown on the supplementary supply active conductor?Medium non-compliance- AS/NZS 4777.1:2024 Clause 8.4.1 (a)
5SB&L22After turning off the “MAIN SWITCH (INVERTER)” does it take less than 2 seconds for current to dissipate from the supplementary supply active conductor?Rectification required- AS/NZS 4777.1:2024 Clause 8.4.1 (b)
Labelling specifics
#CER IDQuestionRatingStandards RefY/N?
1BS42If the lithium-ion pre-assembled BS has a voltage greater than DVC-A, does all cabling and installation requirements meet the requirements for DVC-C if a non-separated PCE other than an inverter is installed? For example, a solar charge controllerRectification required- AS/NZS 5139:2019 Clause 5.3.1.1
2BS63Are the battery system cables flexible cables in accordance with:
a) AS/NZS 5000.2 (450/750 V insulation) for battery systems with a maximum operating voltage less than 450 V DC
b) AS/NZS 5000.1 (0.6/1kV insulation) for battery systems with a maximum operation voltage less than 600 V DC
c) IEC 62930 for battery systems with a maximum operating voltage less than 1500 V DC?
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.2
3BS64Do the cables between the battery system and the PCE meet the requirements of AS/NZS 3000 for selection and installation of wiring systems? If not, is the defect likely to pose a potential safety risk at some stage in the lifetime of the system?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.2
4BS65Do the cables between the battery system and the PCE meet the requirements of AS/NZS 3000 for selection and installation of wiring systems? If not, is the defect not likely to cause a potential safety concern at some stage in the expected lifetime of the system?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.4.2
5BS66If the DC interconnection of the lithium-ion pre-assembled BS to the PCE is not in accordance with AS/NZS 3000, is it such that it constitutes a safety hazard which poses an imminent risk?Unsafe- AS/NZS 5139:2019 Clause 5.3.1.4.2
6BS67Are the cables from the battery system to the PCE:
a) double insulated if the battery system’s maximum voltage exceeds DVC-A
b) double insulated for DVC-A battery systems connected to a non-separated PCE (for example solar charge controller) and where the non-battery side of the PCE is greater than DCV-A?
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.2
7BS68For all battery systems operating at DVC-A, are all cables between the battery system, the overcurrent protection device and the PCE double insulated?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.2
8BS69Are all cables that exit the pre-assembled BS without internal DC overcurrent protection mechanically protected by at least medium duty conduit or equivalent protection up to the over current device?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.3
9BS70For battery systems operating at DVC-B or DVC-C, do the cables between the overcurrent protection device and the PCE have mechanical protection? Refer to AS/NZS 3000:2018 Clause H4.Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.4.3
10BS71Is the voltage drop between the battery system and the PCE no more than 2% based on the rated DC battery port current of the PCE and no more than 5% under any operating conditions?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.4.4
11BS72Is the current-carrying capacity of the pre-assembled battery system’s cable to the overcurrent protection rated to:
a) the maximum current rating of the pre-assembled BS
b) the short-circuit current and duration from the pre-assembled BS?
Rectification required- AS/NZS 5139:2019 Clause 5.3.1.4.5
12BS74If the BESS consists of two or more pre-assembled BS connected in parallel (that do not have a BMS or similar device that provides a managed voltage and current charge/discharge for each separate system), does the output cable from each battery system come to a point where the parallel battery system connects (for example PCE or Junction box) have equal cable resistance?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.4.6
13BS76Does the installation meet the requirements for segregations for AC and DC circuits within enclosures from AS/NZS 3000:2018 Section 3?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.5
- AS/NZS 3000:2018 Section 3
There are four categories relating to the earthing arrangements for battery systems connected to PCEs and each has specific requirements. Please select the appropriate category and inspect to the relevant clause.Information OnlyLogic question
14BS77Where the BS is not directly or resistively earthed to the battery positive or negative conductors and the installation comprises a single BESS with a voltage grater then DVC-A, are all metallic equipment enclosures associated with the BESS installation bonded together to the earthing system of the electrical installation using a minimum bonding conductor size of 6mm2?Medium non-compliance- AS/NZS 5139:2019 Clause 5.3.1.7.3
- AS/NZS 5139:2019 Clause 5.3.1.7.4
15BS78Is the pre-assembled BS earthed according to manufacturer’s instructions?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.7.1
16BS79If system is direct earthed (i.e. has an earth been directly connected to the positive or negative battery conductors), is there a conductor connected to the installation earthing system? The pre-assembled battery system earthing conductor shall be rated to withstand the prospective earth fault current of the battery system for a time at least equal to the operating time of the associated overcurrent protective device.Rectification required- AS/NZS 5139:2019 Clause 5.3.1.6.3
17BS80If the system is resistively earthed (i.e. has an earth cable has been connected in line with a resistor to the positive or negative battery conductors), is one conductor of the battery system connected to the installation earthing system via a resistor? The pre-assembled battery system earthing conductor shall be rated to withstand the prospective earth fault current of the battery system continuously.Rectification required- AS/NZS 5139:2019 Clause 5.3.1.6.4
18BS81If system is connected to a non-separated PCE, does it conform with the requirements of AS/NZS 5139:2019 Clause 5.3.1.6.5?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.6.5
19BS82If the pre-assembled BS is directly earthed (i.e. has an earth been directly connected to the positive or negative battery conductors) with voltages greater than DVC-A, are all metallic equipment enclosures associated with the pre-assembled BS installation bonded together to the earthing system of the electrical installation using a minimum bonding conductor size of 6mm2 or equivalent to the earth conductor size, whichever is the greater?Rectification required- AS/NZS 5139:2019 Clause 5.3.1.7.3
20BS83If the pre-assembled BS is resistively earthed (i.e. has an earth cable has been connected in line with a resistor to the positive or negative battery conductors) with voltages greater than DVC-A, are all metallic equipment enclosures associated with the pre-assembled BS installation bonded together to the earthing system of the electrical installation using a minimum bonding conductor size of 6mm2 or equivalent to the earth conductor size, whichever is the greater?Rectification required-AS/NZS 5139:2019 Clause 5.3.1.7.4
21BS91Are there any accessible live parts? Are any live parts in direct contact with any equipment, component, terminals or connection, that are tested to be LIVE and accessible by one action to be touched?Unsafe- AS/NZS 3000
22BS92Are there connectors, couplings, covers or components able to be removed without the use of a tool which provide access to live parts?Rectification required- AS/NZS 3000
23BS93Has all electrical work associated with the installation of the lithium-ion pre-assembled integrated BS been installed in line with Australian standards? If not, is the defect likely to pose a potential safety risk at some stage in the lifetime of the system?Rectification required- AS/NZS 3000
- AS/NZS 5139
- AS/NZS 5033
- AS/NZS 4777.1
24BS94Has any electrical work associated with the installation of the lithium-ion pre-assembled integrated BESS not been installed in line with Australian standards such that it is not likely to cause a potential safety hazard now or for the expected lifetime of the system?Medium non-compliance- AS/NZS 3000
- AS/NZS 5139
- AS/NZS 5033
- AS/NZS 4777.1
25BS95Has any electrical work associated with the installation of the lithium-ion pre-assembled BS not been installed in line with Australian standards such that it constitutes a safety hazard which poses an imminent risk?Unsafe- AS/NZS 3000
- AS/NZS 5139
- AS/NZS 5033
- AS/NZS 4777.1
26BS96Are there any loose connections in pre-assembled BS and associated wiring with NO signs of heat?Rectification required- AS/NZS 5139 5.4.2.2
27BS97Are there any loose connections in pre-assembled BS and associated wiring WITH signs of heat?Unsafe- AS/NZS 5139 5.4.2.2
Expand...
#CER IDQuestionRatingStandards RefY/N?
1DOC1Has a full system manual incorporating all components of AS/NZS 5139:2019 Clause 6.4.1.2 been provided to the home owner?Medium non-complianceAS/NZS 5139:2019 Clause 6.4.1.2